When processors and accelerators draw hundreds of watts and a rack draws tens of kilowatts, air can no longer keep up: it would have to be forced through the servers in huge volumes. At the same volume a liquid carries away thousands of times more heat, so it is routed straight to the chips, or entire servers are submerged in it.
Direct-to-chip cooling
Cold plates are fitted onto the hottest components — processors and GPUs: copper or aluminium heat exchangers with channels that water flows through. The server itself stays ordinary: boards, memory and drives work as before, while the liquid is fed in through tubes and manifolds via quick-disconnect couplings — their interface is standardised by the OCP (the UQD specification, Universal Quick Disconnect). Outside the server sits a coolant distribution unit (CDU): it moves heat from the server loop into the building loop, keeping the liquids separate so that a leak in the server hall does not flood the equipment.
- the cold plate draws heat off the chip
- tubes and manifolds collect the warmed water from the rack’s servers
- the CDU passes the heat into the second loop
- the building loop releases the heat outdoors — to a cooling tower, a chiller or the heating system
The liquid runs warm — about 30–45 °C — so chillers are often not needed: the heat is rejected to outdoor air or to a dry cooler. The water is purified and dosed with propylene glycol: in the OCP specifications the typical coolant is PG25, an aqueous solution of propylene glycol.
Immersion cooling
Servers are submerged whole in a tank filled with a dielectric — a liquid that does not conduct electricity: synthetic oils, esters, polyalphaolefins or fluorocarbons. There are no fans in the servers; heat is drawn off by the entire surface of the boards.
| Feature | Single-phase | Two-phase |
|---|---|---|
| What happens | the liquid heats up and is pumped to a heat exchanger | the liquid boils; the vapour condenses on the cold lid of the tank |
| Liquid | oils, esters, polyalphaolefins | fluorocarbons with a low boiling point |
| Servicing | the server is lifted out of the tank and the liquid drains off | the tank remains closed; the vapour condenses and stays inside |
Why the switch to liquid
A rack of ordinary servers draws 20–30 kW, and air cooling normally copes with that. Racks with AI accelerators already need more than 100 kW: the NVIDIA GB200 NVL72 rack, with 36 CPUs and 72 GPUs, is designed for liquid cooling from the start. As density grows, liquid stops being an option and becomes a condition of the rack working at all: it also cuts floor space and the energy spent on cooling, bringing PUE closer to one.
Liquid cooling for servers is nothing new: in the IBM 3081 mainframe (1980) the chips were cooled by water-cooled plates, and in the Cray-2 supercomputer (1985) the boards were submerged in the inert liquid Fluorinert. Growing AI workloads brought it back into data centres at scale: the Open Compute Project runs a Cooling Environments project with specifications for cold plates, CDUs, immersion, rear-door heat exchangers and heat reuse.
Sources
the term is written from these pages- OCP — Cooling Environments Projectopencompute.org/projects/cooling-environments/(opens in a new tab)