Liquid cooling

A method of removing heat from electronics in which a liquid — water or a dielectric — carries the heat away instead of air; used where power density exceeds what air cooling can handle.

Also: direct liquid cooling, DLC, water cooling

checked 9 Nov

All terms

When processors and accelerators draw hundreds of watts and a rack draws tens of kilowatts, air can no longer keep up: it would have to be forced through the servers in huge volumes. At the same volume a liquid carries away thousands of times more heat, so it is routed straight to the chips, or entire servers are submerged in it.

Direct-to-chip cooling

Cold plates are fitted onto the hottest components — processors and GPUs: copper or aluminium heat exchangers with channels that water flows through. The server itself stays ordinary: boards, memory and drives work as before, while the liquid is fed in through tubes and manifolds via quick-disconnect couplings — their interface is standardised by the OCP (the UQD specification, Universal Quick Disconnect). Outside the server sits a coolant distribution unit (CDU): it moves heat from the server loop into the building loop, keeping the liquids separate so that a leak in the server hall does not flood the equipment.

  1. the cold plate draws heat off the chip
  2. tubes and manifolds collect the warmed water from the rack’s servers
  3. the CDU passes the heat into the second loop
  4. the building loop releases the heat outdoors — to a cooling tower, a chiller or the heating system

The liquid runs warm — about 30–45 °C — so chillers are often not needed: the heat is rejected to outdoor air or to a dry cooler. The water is purified and dosed with propylene glycol: in the OCP specifications the typical coolant is PG25, an aqueous solution of propylene glycol.

Immersion cooling

Servers are submerged whole in a tank filled with a dielectric — a liquid that does not conduct electricity: synthetic oils, esters, polyalphaolefins or fluorocarbons. There are no fans in the servers; heat is drawn off by the entire surface of the boards.

FeatureSingle-phaseTwo-phase
What happensthe liquid heats up and is pumped to a heat exchangerthe liquid boils; the vapour condenses on the cold lid of the tank
Liquidoils, esters, polyalphaolefinsfluorocarbons with a low boiling point
Servicingthe server is lifted out of the tank and the liquid drains offthe tank remains closed; the vapour condenses and stays inside

Why the switch to liquid

A rack of ordinary servers draws 20–30 kW, and air cooling normally copes with that. Racks with AI accelerators already need more than 100 kW: the NVIDIA GB200 NVL72 rack, with 36 CPUs and 72 GPUs, is designed for liquid cooling from the start. As density grows, liquid stops being an option and becomes a condition of the rack working at all: it also cuts floor space and the energy spent on cooling, bringing PUE closer to one.

Liquid cooling for servers is nothing new: in the IBM 3081 mainframe (1980) the chips were cooled by water-cooled plates, and in the Cray-2 supercomputer (1985) the boards were submerged in the inert liquid Fluorinert. Growing AI workloads brought it back into data centres at scale: the Open Compute Project runs a Cooling Environments project with specifications for cold plates, CDUs, immersion, rear-door heat exchangers and heat reuse.

Sources

the term is written from these pages

Verified 9 Nov

Not to be confused with

what it is mixed up with and how it differs

  • TDPthermal design power

    TDP is the design thermal power of a chip that the cooling system has to dissipate; liquid cooling is a way of doing that.

In depth in the references

where the topic is covered in detail