Racks come in a fixed height while servers and switches are made in different ones, so both the devices and the rack itself are measured in the same units — rack units. A typical server rack holds 42U, and devices usually take up 1U to 4U.
What one unit is
The unit comes from the EIA-310 standard, “Cabinets, Racks, Panels, and Associated Equipment”, which sets the dimensions of 19-inch racks. One unit is 1¾ inches, that is 44.45 mm: the space taken by a group of three holes in the vertical rails, spaced 15.875 + 15.875 + 12.7 mm apart. The chassis itself is made slightly shorter than the units allotted to it: a 1U panel is about 43.7 mm tall so that neighbouring devices do not touch when installed.
Typical sizes
| Equipment | Height in units |
|---|---|
| Access switch, thin server | 1U |
| Typical rack server | 1U–2U |
| GPU server, disk shelf | 2U–4U |
| Rack-mount UPS | from 1U |
| Typical server rack | 42U |
Rack units describe height only. The 19-inch mounting width is taken for granted, while depth and weight are unique to each device and are counted separately, as is the rack’s load rating. Data centres also use racks taller than 42U — 48U, for example.
Planning rack space
The heights of all devices in rack units are added up and subtracted from the rack’s capacity, leaving headroom: for airflow, cables, shelves and equipment to be added later. A 42U rack is never filled with 42 devices of 1U each: after the servers, switches and patch panels only a few units remain free.
The notation is U or RU (rack unit): 1U, 2U, 42U. The international counterpart of the standard is the IEC 60297 series for 19-inch mechanical structures.