A PDU is a power strip in a data centre rack, the second-to-last stop on electricity’s way to the server: power comes in from a UPS or a distribution board, then the PDU spreads it across outlets, and from there the current reaches the server power supplies. The type of PDU determines whether an engineer can see consumption down to an individual outlet and reboot a hung device without leaving their desk.
Types of PDU
| Type | What it does |
|---|---|
| Basic | distributes power only: outlets, overload protection, no data |
| Metered at the input | shows total current and voltage at the input, helping to keep the line below its limit |
| Switched | lets you turn individual outlets on and off over the network — remotely reboot a server |
| Per-outlet metered | measures consumption per outlet: you can see how much power each server draws |
| With built-in ATS | has two inputs and switches itself to the reserve line for single-PSU devices |
| Transfer switch | a standalone device with an ATS: feeds the whole cabinet from one of its two inputs |
Networked PDUs
A networked (intelligent) PDU is one that is connected to the network and exposes its data: input measurements, per-outlet readings and readings after the PDU’s circuit breakers, power state, and temperature and humidity sensor readings at the rack. It is a networked model that shows a line creeping towards its current limit long before protection trips. Measurements and outlet switching are available over SNMP and Redfish, so such PDUs are built into monitoring systems: a script can issue a “switch the outlet off” command or receive an overload alert.
Two power lines
In a fault-tolerant rack there are two PDUs — A and B, each fed from its own power line with its own UPS. Servers with dual power supplies are connected so that the first PSU plugs into PDU A and the second into PDU B: losing an entire line then goes unnoticed by the workloads. Single-PSU devices in such a rack get a transfer switch with an ATS that switches itself to the reserve input. This scheme is called 2N: two independent power chains from the input to the outlet.
The abbreviation PDU is also found in networking, meaning protocol data unit; it has nothing to do with power.